Neutralisation calculator

How much alkali to neutralise an acidic stream, or how much acid for an alkaline one. Measure the stream's strength by titration for the best answer; a pH reading only works for strong acids or alkalis.

How it works

Stream strength from a titration: N = titrant used (mL) × titrant N ÷ sample (mL). Equivalents to neutralise = volume (L) × N. Chemical needed (kg) = equivalents × molar mass ÷ n ÷ 1,000 ÷ purity.

Worked example: 100 mL of an acidic effluent takes 50 mL of 0.1 N NaOH to reach pH 7, so it is 0.05 N. 10 m³ of it holds 10,000 × 0.05 = 500 equivalents. That needs 500 × 40.00 ÷ 1,000 = 20 kg of NaOH, which is 41.7 kg (27.6 L) of 48% lye, or about 20.6 kg of 90% hydrated lime.

Effluents with weak acids, buffers or metals take more chemical than their pH suggests. That is why the titration route is the default.

Safety when diluting and neutralising

  • Add acid to water, never water to acid. Concentrated sulphuric acid and caustic lye release a lot of heat; add them slowly with stirring, in a vessel rated for the temperature.
  • Wear goggles or a face shield, chemical gloves and an apron. Keep an eyewash and running water nearby.
  • Dissolving caustic flakes is also strongly exothermic. Add the flakes to cold water in small portions.
  • Neutralise in steps: dose about 80% of the calculated amount, mix, check pH, then add the rest.
  • Check each chemical's SDS before use. Our product documents are on the SDS and specification sheets page.

Questions about this calculator

Can I use pH to work out how much alkali an effluent needs?

Only for a clean, strong acid. Most effluents contain weak acids, buffers or metal salts that need far more alkali than the pH suggests. Titrate a sample to pH 7 and use the titration option in the calculator.

Why dose about 80% first?

Real streams vary and buffers can hide the end-point. Dosing about 80% of the calculated amount, mixing, checking pH and then adding the rest avoids overshooting.

Need the chemical, not just the numbers?

Tell us what you are making or treating. We supply Sun Brand polymers from Chennai, and the full industrial chemical range through surajchemicals.com.