How it works

1 °dH = 17.85 mg/L as CaCO₃, 1 °fH = 10 mg/L, 1 °Clark = 14.25 mg/L and 1 US grain per gallon = 17.12 mg/L. Hardness as CaCO₃ = 2.497 × calcium + 4.118 × magnesium, in mg/L.

Worked example: 60 mg/L calcium and 20 mg/L magnesium = 149.8 + 82.4 = 232 mg/L as CaCO₃, which is hard water and above the IS 10500 acceptable limit of 200 mg/L (the permissible limit is 600 mg/L where there is no alternative source).

Conversion factors

UnitEquals (mg/L as CaCO₃)
1 °dH (German)17.848
1 °fH (French)10.00
1 °Clark (English)14.254
1 grain per US gallon17.118
1 mmol/L100.09
1 meq/L50.045

Common scale: soft under 60, moderately hard 60–120, hard 120–180, very hard over 180 mg/L as CaCO₃. IS 10500 allows 200 mg/L as acceptable and 600 mg/L as permissible where there is no alternative source.

Questions about this calculator

How do I convert water hardness units?

1 °dH = 17.85 mg/L as CaCO₃, 1 °fH = 10 mg/L, 1 °Clark = 14.25 mg/L and 1 US grain per gallon = 17.12 mg/L. Hardness as CaCO₃ = 2.497 × calcium + 4.118 × magnesium (mg/L).

Why does hardness matter in a plant?

Calcium and magnesium form scale on hot surfaces and in RO membranes, so hardness decides whether you need softening or an antiscalant.

Need the chemical, not just the numbers?

Tell us what you are making or treating. We supply Sun Brand polymers from Chennai, and the full industrial chemical range through surajchemicals.com.